Vortex enclosure & cabinet coolers
IP-66


general characteristics:

Totally maintenance-free enclosure & cabinet cooling devices with no moving parts.
Made of AISI 304 stainless steel. Operated by clean, dry compressed air.

how do vortex tubes work?

A Vortex Tube is a device with no moving parts that will convert any stream of compressed air into two streams – one hot and one cold.

A Vortex tube can produce cold air down to -35C and hot air up to +127C.

Clean, dry compressed air is injected tangentially into the tube at sonic speed and creates a cyclone (Vortex) spinning at about one million revolutions per minute.
Part of the air is forced to spin inward to the centre hole and travels up the long tube where a valve turns this spinning column (Vortex) of air inside itself.
The inside column of air gives up its heat to the outside column.
The cold air is then directed out the cold end of the Vortex Tube.
The temperature and air flow are totally controllable by adjusting the valve at the hot end of the tube.

 

 

 

 

 

 

 

 

 

  

 
 

 

selection table:

stainless steel vortex cabinet cooler - fixed state (with ducting kit)

Ref. No:

description:

inlet pressure
kPa

air consumption l/min

cooling capacity:

Watt

BTU/h

kcal/h

V22025

Vortex Cooler, 35scfm, fixed 700 704 480 1500 380
stainless steel vortex tubes - adjustable:

V10008

Vortex Tube, 8scfm, adjustable

700

225

125

400

100

V10010

Vortex Tube, 10scfm, adjustable

700

282

190

600

150

V10015

Vortex Tube, 15scfm, adjustable

700

423

285

900

230

V10025

Vortex Tube, 25scfm, adjustable

700

704

480

1500

380

V10035

Vortex Tube, 35scfm, adjustable

700

986

795

2500

630

accessories:

NSYCCOTHO

Thermostat with N/O contact; 230 VAC; 10A

V10000

Cold end muffler

V10001

Hot end muffler
   

performance data:

inlet pressure kPa

temperature

cold fraction: (the percentage of the total flow which comes out as cold air - 60% is typical)

20%

30%

40%

50%

60%

70%

80%

140

drop

17.3 C

16.3 C

13.4 C

10.7 C

7.0 C

2.8 C

1.8 C

increase

9.4C

4.2 C

3.2 C

10.7 C

18.4 C

28.1 C

42.3 C

280

drop

31.8 C

29.9 C

27.3 C

22.9 C

17.3 C

11.4 C

4.0 C

increase

4.8 C

1.8 C

11.2 C

22.9 C

33.8 C

47.2 C

64.6 C

410

drop

40.2 C

38.8 C

34.3 C

29.0 C

23.1 C

16.1 C

7.5 C

increase

3.6 C

4.4 C

15.1 C

29.0 C

40.1 C

56.2 C

76.2 C

550

drop

47.3 C

44.6 C

39.1 C

33.5 C

27.4 C

19.0 C

10.1 C

increase

3.3 C

6.7 C

17.8 C

33.5 C

45.6 C

62.4 C

82.9 C

700

drop

53.5 C

48.7 C

44.0 C

38.0 C

30.3 C

22.2 C

12.0 C

increase

2.3 C

7.8 C

19.6 C

38.0 C

48.9 C

66.2 C

89.0 C

based on inlet air temperature of 21 C this chart gives approximate temperature drops and rises from the inlet air temperature

 
 

NSYCCOTHO
thermostat

air controls

NSYCAG38LP vents

In order for the vortex tube to work efficiently, the enclosure needs to be vented to allow through-flow
of air.
This can be achieved by fitting vents or louvres on the enclosure

 

ventilation louvres (IP 23):

Ref. No:

dimensions:

louvre width:

NSYCAG104x95LM

120x120mm

70mm

NSYCAG130x110LM

160x160mm

100mm

NSYCAG1740x190LM

220x220mm

180mm

 

 
 
 
 